FS720 Fire System Architectures

FS20 fire detection systems can be connected to Desigo CC to implement various configurations. The following are examples of valid system architectures.

Stand-Alone and Client/Server Systems

Systems for FS20 fire networks can be configured as a stand-alone management station or client/server network-distributed system.

In single station systems, the FCnet/SAFEDLINK fire network is connected to the unique management station via the GAP unit.

In local client/server solutions, the connection to the fire network is implemented on the server station that provides communication services to client stations.

Client/server solutions can also support multiple FCnet/SAFEDLINK fire networks connected to the server station over a network. Additional client and FEP stations may be installed.

Example of a large, multi-network, client/server system

SAFEDLINK Network

FS20 control panels (FC20) and terminals (FT20) are networked together on a SAFEDLINK, a fast and redundant network designed for fault-tolerant fire protection solutions that applies the specialized FCnet protocol.

Example of Fire SAFEDLINK Network

Service Engineering

In the system configuration, you must define a network data structure (BACnet) as one of the Field Networks of the system to allow for the control panels data (SiB-X XML metafiles) to be imported and populate the management station database.

The tool can be connected to any FC20 panel (except the GAP) or to the Ethernet switch.

Engineering Service PC Connection