System Limits
- 1 NK823x per BACnet network
- 4 fire systems (FG700A) per NK823x (depending on NK823x hardware features), and max. 50 fire subsystems (FT700A, FC700A, FG700A) per NK823x
- 16 subsystems (FT700A, FC700A, FG700A) per fire system
- 2 FG700A gateways per fire system
- Max. 25,000 objects (~10,000 physical points) per NK823x
Compatibility Information
- Panel firmware / tool version: 762 / SWE700A V1.35.0-000.